2018-02-09

# 40

KhNPP 1
Electricity production
 
 per day: 24.25 mln.kW*h 
 
 since the beginning of month: 48.67 mln. kW*h 
 
 since the beginning of quarter: 48.67 mln. kW*h 
 
 since the beginning of year: 48.67 mln. kW*h 
 
 electricity utilization for auxiliaries: 4.29 % 
 
General characteristics
 
 
 Hours worked: 2.1 ef. days 
 
 Campaign: 301.3 ef. days 
 
 Performance factor (net)of the unit: 32.42 % 
 
 Electrical power (average daily): 1010.4 MW 
 
 The temperature of circulating water at the inlet:  24.4  o, C 
 
KhNPP 2
Electricity production
 
 per day: 24.32 mln.kW*h 
 
 since the beginning of month: 218.42 mln. kW*h 
 
 since the beginning of quarter: 831.39 mln. kW*h 
 
 since the beginning of year: 831.39 mln. kW*h 
 
 electricity utilization for auxiliaries: 4.21 % 
 
General characteristics
 
 
 Hours worked: 101.6 ef. days 
 
 Campaign: 323 ef. days 
 
 Performance factor (net)of the unit: 32.77 % 
 
 Electrical power (average daily): 1013.4 MW 
 
 The temperature of circulating water at the inlet:  24.5  o, C 
 
Operating mode of heating system
 
  direct  reverse  
 temperature : 7856 o, C 
 
 t of outside air: -1.9 o, C 
 
Emission in ventiduct
 
 long-lived nuclides:  2.49*10+04 Bq /day   MPE*  1,00*10+09  Bq /day 
 
 short-lived nuclides:  . Bq /day   MPE:  not regulated  Bq /day 
 
 Inert gases:  2.98*10+10 Bq /day   MPE:   4,60*10+13  Bq /day 
 
 Iodine:  2.49*10+04 Bq /day   MPE:   4,60*10+09  Bq /day 
 * - maximum permissible emission 
Water utilization
 
 on the town: 6961 m3 
 
 on construction yard: 1 m3 
 
 on industrial site: 366 m3